Specification data

Flyway™ patterns & specs

Everything you need to write Flyway into a specification: geometry, spacing, gloss, substrate options and unit configurations. All five patterns were evaluated by the American Bird Conservancy and the Bird-Safe Buildings Alliance and found to satisfy ABC's criteria for bird-friendly materials.

At a glance

Common to all five patterns: a permanent etch on surface 1, gloss < 6 at 60°, acceptable on any vision glass or tinted glass unit, with all coatings behind the surface 1 etch. Any lite size, as long as it is under 72″ in at least one dimension.

Flyway bird-safe glass pattern specifications and assigned Threat Factors
Pattern Marker Spacing (o.c.) Orientation Gloss @ 60° Threat Factor™
A6 mm dots (∅ ¼″)2.00″ × 2.00″ gridGrid< 620
B6 mm dots (∅ ¼″)2.00″ vert. × 4.00″ horiz.Grid< 625
C3 mm lines (⅛″ wide)2.00″ o.c. · 1.875″ gapVertical, full height< 620
D3 mm lines (⅛″ wide)4.00″ o.c. · 3.875″ gapVertical, full height< 625
E3 mm lines (⅛″ wide)2.00″ o.c. · 1.875″ gapHorizontal, full width< 620

Threat Factor™ is a trademark of the American Bird Conservancy. Lower is better; ABC's bird-friendly threshold is 30 or below. Ratings assigned by evaluation are conservative maximums. See how the rating was assigned.

Pattern detail

Swatches are drawn to scale. Each square shows a 12″ × 12″ field of glass at true marker size and spacing.

A

6 mm dots, 2″×2″

TF 20
Marker
6 mm dot, ∅ ¼″ (0.0491 in²)
Spacing
2.00″ o.c. horizontal, 2.00″ o.c. vertical
Diagonal
2.83″ o.c.
Surface
Surface 1
Gloss
< 6 at 60°

Our default recommendation. Densest coverage, best rating, and the pattern that most directly answers a 2″ × 2″ ordinance rule.

B

6 mm dots, 2″×4″

TF 25
Marker
6 mm dot, ∅ ¼″ (0.0491 in²)
Spacing
4.00″ o.c. horizontal, 2.00″ o.c. vertical
Diagonal
4.47″ o.c.
Surface
Surface 1
Gloss
< 6 at 60°

Half the marks of Pattern A. The most visually open dot option, still comfortably inside the bird-friendly threshold.

C

Vertical lines, 2″

TF 20
Marker
3 mm line, ⅛″ wide
Spacing
2.00″ o.c., 1.875″ clear gap
Run
Continuous, full height
Surface
Surface 1
Gloss
< 6 at 60°

Reads as a fine reeded texture at close range and nearly disappears at distance. Sits naturally with vertical mullion rhythm.

D

Vertical lines, 4″

TF 25
Marker
3 mm line, ⅛″ wide
Spacing
4.00″ o.c., 3.875″ clear gap
Run
Continuous, full height
Surface
Surface 1
Gloss
< 6 at 60°

The lightest touch in the range. For facades where the glazing has to stay as quiet as the architect intended.

E

Horizontal lines, 2″

TF 20
Marker
3 mm line, ⅛″ wide
Spacing
2.00″ o.c., 1.875″ clear gap
Run
Continuous, full width
Surface
Surface 1
Gloss
< 6 at 60°

Same rating as Pattern C with a horizontal emphasis, which is the right choice on banded or spandrel-heavy elevations.

Choosing between them

Need the best number? A, C or E, all at Threat Factor 20.

Need the most open glass? D, then B.

Ordinance says 2″×2″? Pattern A.

Vertical facade? C or D. Banded facade? E.

Send us an elevation →

Substrates & glass makeups

The ABC evaluation covers the etch pattern, and states plainly that the patterns are acceptable on any vision glass or tinted glass unit, with all coatings behind the surface one etch. Practically, that means:

  • Clear float, low-iron, gray, bronze, blue and other tints
  • Monolithic, laminated, tempered and heat-strengthened
  • Insulating glass units in any configuration
  • Low-E and solar-control coatings, positioned behind the etch
  • Any lite size, as long as one dimension is under 72″
Size limit: under 72″ in at least one direction. The other dimension can run as long as the lite needs to. A 60″ × 120″ lite works; an 84″ × 84″ lite does not. Larger than that? Send us the elevation and we'll talk options.

The evaluated sample was 12″ × 12″ monolithic clear glass; the approval extends the patterns beyond that specific makeup.

Insulating glass units

Two ways to get Flyway on an IG unit, and the choice usually comes down to whether your project requires IGCC certification.

Option 1: Certified IG partner

Your IG unit is built by an IGCC-certified manufacturer such as Oldcastle, and we apply the Flyway etch to surface 1. Use this where IGCC certification is required.

Option 2: We build the unit

We fabricate the IG unit here to whatever configuration you want, then etch it. Faster, simpler and a single source. Where the spec calls for certification, Option 1 is the route.

Provenance

How the rating was assigned

Worth understanding before you defend the number in a submittal review.

Evaluation, not tunnel test

ABC partners with the Bird-Safe Buildings Alliance, a group of architects experienced in bird-friendly design, conservation biologists and collision experts, to assign Threat Factors™ to materials similar to those already rated. Flyway was rated through this evaluation protocol.

Evaluation ratings are conservative by design

In ABC's words, these ratings are “very conservative: the rating assigned is the maximum expected TF; lower ratings might be obtainable through actual tunnel testing, product dependent.” A Flyway Threat Factor of 20 is a ceiling, not a midpoint.

A Threat Factor can be assigned by evaluation to products that:

  • a. are demonstrably similar or identical to products tested in the past;
  • b. were tested using other peer-reviewed protocols ABC and BSBA have determined to be equivalent or translatable to tunnel testing scores;
  • c. were studied by scientists or experienced building collision monitors with a documented reduction in collisions of at least 50%; or
  • d. meet ABC's Prescriptive Rating Criteria, derived from tunnel scores, collision monitoring data and the literature on avian perception.
Evaluation record
ProtocolABC / Bird-Safe Buildings Alliance Evaluation
Evaluation periodJune to August 2026
Report dateAugust 26, 2026
SubmittedFive surface-1 etch patterns
OutcomeAll five samples found to satisfy ABC's criteria for bird-friendly glass and/or materials
Assigned Threat Factors™20 (Patterns A, C, E) · 25 (Patterns B, D)
For the spec writer

Guide specification

A complete, editable glazing section in CSI three-part format. Copy it straight into your project manual and delete the options that don't apply. We'll review a draft section at no charge before it goes out to bid.

Section 08 80 00: Bird-friendly glazing
SECTION 08 80 00 - GLAZING
BIRD-FRIENDLY GLAZING

PART 1 - GENERAL

1.1  SUMMARY
     A.  Section includes bird-friendly glazing with permanent visual
         markers applied to surface 1.

1.2  REFERENCES
     A.  American Bird Conservancy (ABC) Bird-Friendly Materials
         Evaluation Program - Material Threat Factor rating.
     B.  ASTM C1036 - Standard Specification for Flat Glass.
     C.  ASTM C1048 - Heat-Treated Flat Glass.

1.3  SUBMITTALS
     A.  Product Data: Manufacturer's data for each glazing type.
     B.  Samples: 12" x 12" sample of each specified pattern on the
         proposed glass makeup.
     C.  Evaluation Report: ABC / Bird-Safe Buildings Alliance evaluation
         report showing the assigned Threat Factor for each pattern.
     D.  Shop Drawings: Elevations showing pattern extents, coverage
         limits, and treatment of transoms, corners and returns.

1.4  QUALITY ASSURANCE
     A.  Fabricator: Single firm performing glass fabrication and
         marker application, with not less than 5 years of experience.
     B.  Mockup: Provide one full-size unit for review prior to
         fabrication of remaining units when required by the Architect.

1.5  WARRANTY
     A.  Marker Warranty: Markers shall be integral to the glass
         surface and shall not delaminate, peel or wear off.

PART 2 - PRODUCTS

2.1  MANUFACTURER
     A.  Basis of Design: Flyway Bird-Safe Glass by River City
         Creative Glass, 3550 W 145th St, Burnsville, MN 55306.
         Telephone 952-224-9030.

2.2  PERFORMANCE REQUIREMENTS
     A.  Provide bird-friendly glazing with visual markers applied to
         surface 1 having a material Threat Factor of 25 or lower as
         assigned by the American Bird Conservancy.
     B.  Markers shall be applied to surface 1. Low-E and other
         coatings shall be located behind the surface 1 marker.

2.3  MATERIALS
     A.  Marker Type: Permanent etched marker, applied to
         surface 1.
     B.  Gloss: Less than 6 at 60 degrees.
     C.  Substrate: Any vision or tinted glass unit. Clear, low-iron,
         tinted, laminated, and insulating units are acceptable.

2.4  PATTERNS
     A.  Pattern: [Select one]
         1.  Pattern A - 6 mm dots at 2" x 2" grid. Threat Factor 20.
         2.  Pattern B - 6 mm dots at 2" x 4" grid. Threat Factor 25.
         3.  Pattern C - 3 mm vertical lines at 2" o.c. TF 20.
         4.  Pattern D - 3 mm vertical lines at 4" o.c. TF 25.
         5.  Pattern E - 3 mm horizontal lines at 2" o.c. TF 20.

2.5  INSULATING GLASS UNITS
     A.  [Option 1] Insulating glass units shall be IGCC-certified
         units furnished by others and etched by the bird-friendly
         glazing fabricator.
     B.  [Option 2] Insulating glass units shall be fabricated by the
         bird-friendly glazing fabricator to the configuration
         scheduled.

PART 3 - EXECUTION

3.1  EXAMINATION
     A.  Verify openings are plumb, square and within tolerance prior
         to glazing.

3.2  INSTALLATION
     A.  Install units with the marked surface oriented outboard
         (surface 1) in every opening. Units installed with the
         marker inboard do not provide the specified performance.

3.3  CLEANING AND PROTECTION
     A.  Clean with mild detergent and water. Do not use abrasive
         cleaners, scrapers or blades on the etched surface.

END OF SECTION

Sample language for a mockup. Confirm final wording against your project's governing ordinance and rating-system requirements before issuing.

Specifying insulating glass units. We supply the unit through an IGCC-certified partner where the project requires certification, or fabricate it here to any configuration you want. Where the spec requires IGCC certification, use Option 1 in article 2.5 and have the units furnished to us.

Send us an elevation.

We'll come back with a pattern recommendation, a layout drawing and a price.